Line 25: Line 25:
 ===== 1. Description ===== ===== 1. Description =====
  
-This class C device transmits the state of its 16 inputs (12-24Vac/dc) and controls 8 outputs (5A - 230Vac) through the LoRaWAN(r) network. All these inputs and outputs are galvanically isolated. It can be used for industrial process control, home automation, water treatment, agriculture irrigation and similar applications.+This class C device transmits the state of its 16 inputs (12-24Vac/dc) and controls 8 outputs (up to 5A - 230Vac) through the LoRaWAN(r) network. All these inputs and outputs are galvanically isolated. It can be used for industrial process control, home automation, water treatment, agriculture irrigation and similar applications.
  
 {{ :wiki:manual_mcf-lw13mio:mcf-lw13mio.jpg?400 |}} {{ :wiki:manual_mcf-lw13mio:mcf-lw13mio.jpg?400 |}}
Line 46: Line 46:
   * Power supply 24Vac/dc   * Power supply 24Vac/dc
   * Maximum power consumption 8W   * Maximum power consumption 8W
-  * 16 opto-isolated input AC-DC, range 5-24Vac/dc +  * 16 opto-isolated input AC-DC, range 5-28Vac/dc 
-  * 8 relay output with COM, NO, NC contacts carrying 5Amp@230Vac~+  * 8 relay output with COM, NO(5Amp@230Vac), NC(3Amp@230Vac)
   * USB for node setup ad FW upgrade   * USB for node setup ad FW upgrade
   * Storage temperature range -20°C ÷+80°C   * Storage temperature range -20°C ÷+80°C
Line 76: Line 76:
 {{ :wiki:manual_mcf-lw13mio:label_supply.jpg?nolink&400 |}} {{ :wiki:manual_mcf-lw13mio:label_supply.jpg?nolink&400 |}}
  
-^  **Name**  ^  **Description**                        ^ +^  **Connector**^  **Pin**^  **Name**  ^  **Description**                        ^ 
-| VSS        | Vss reference, power supply **dc (-)**  | +|J3  | 9     | VSS        | Vss reference, power supply **dc (-)**  | 
-| VSS        | Vss reference, power supply **dc (-)**  | +|::: | 10    | VSS        | Vss reference, power supply **dc (-)**  | 
-| VAC1       | Power supply **ac and dc (+)**          | +|:::  | 11   | VAC1       | Power supply **ac and dc (+)**          | 
-| VAC2       | Power supply **ac only**                |+| ::: | 12   | VAC2       | Power supply **ac only**                |
  
-Valid range is 24Vac/dc ± 10% +**Valid range is 24Vac/dc ± 10% **\\
 Maximum power consumption: 8W Maximum power consumption: 8W
  
Line 108: Line 108:
  
  
-enginko provides user manuals, javascript examples, downlink generator, uplink decoder, different tools and, upon free registration, firmware updates :+Angel4Future provides user manuals, javascript examples, downlink generator, uplink decoder, different tools and, upon free registration, firmware updates :
  
  
Line 160: Line 160:
 | On Voltage                  | >5Vac/dc   | | On Voltage                  | >5Vac/dc   |
 | Maximum input voltage       | 28Vac/dc  | | Maximum input voltage       | 28Vac/dc  |
-| Input current               5mA typ    |+| Input current               6mA typ    |
 | Max frequency (as counter)  | 2Hz       | | Max frequency (as counter)  | 2Hz       |
 | Optoinsulation              | 2500Vac (1 min)   | | Optoinsulation              | 2500Vac (1 min)   |
Line 218: Line 218:
  
 |Contact mode  |SPDT  | |Contact mode  |SPDT  |
-|Max. power commutable  |1250VA  |+|Max. power commutable  |1250VA (NO) | 
 +|:::  |750VA (NC)|
 |Maximum switching voltage  |250Vac~  | |Maximum switching voltage  |250Vac~  |
 |Minimum switching load mW |500mW (10V/5mA)  | |Minimum switching load mW |500mW (10V/5mA)  |
Line 297: Line 298:
 {{ :wiki:loraweb:loraweb_lora.jpg?direct&600 |}} {{ :wiki:loraweb:loraweb_lora.jpg?direct&600 |}}
  
-The device exits factory activated with **NONE** mode.+The device exits factory activated with **OTAA ENGINKO** mode.
 On request devices can be shipped aleady activated. On request devices can be shipped aleady activated.
  
Line 317: Line 318:
  
    
-==== 5 Configuration ====+===== 5 Configuration =====
  
 {{ :wiki:manual_mcf-lw13mio:mio_loraweb_general.jpg?direct&600 |}} {{ :wiki:manual_mcf-lw13mio:mio_loraweb_general.jpg?direct&600 |}}
Line 402: Line 403:
  
  
-To bring back the sensor to factory default and reset the passwords, a reset code must be requested to enginko (please provide the DevEUI of the sensor when you ask for that code).+To bring back the sensor to factory default and reset the passwords, a reset code must be requested to Angel4Future (please provide the DevEUI of the sensor when you ask for that code).
  
 ===== 7 Configuration file =====  ===== 7 Configuration file =====
  
-With LoRaWEB is possible to configure the device using an XML file, instead to manually adjust the parameters (for details about the file format please ask to enginko). This is very useful especially in +With LoRaWEB is possible to configure the device using an XML file, instead to manually adjust the parameters (for details about the file format please ask to Angel4Future). This is very useful especially in 
 case of multiple devices configuration. case of multiple devices configuration.
  
-With "Save" button an XML file with the actual configuration of the sensor will be generated. This is useful to store or clone the configuration, or to send it to enginko's support if needed.+With "Save" button an XML file with the actual configuration of the sensor will be generated. This is useful to store or clone the configuration, or to send it to Angel4Future's support if needed.
  
  
Line 433: Line 434:
  
  
-For details on files format please ask to enginko.+For details on files format please ask to Angel4Future.
 ===== 8 LoRaWEB Tool ===== ===== 8 LoRaWEB Tool =====
  
-enginko provides, upon free registration, **LoRaWEB** online tool,  where for each sensor it is possible to find documentation, javascript examples for parsing, downlink generator and uplink decoder:+Angel4Future provides, upon free registration, **LoRaWEB** online tool,  where for each sensor it is possible to find documentation, javascript examples for parsing, downlink generator and uplink decoder:
  
 [[https://iot.mcf88.cloud/LoRaWeb/#/configuration|LoRaWEB Tool]] [[https://iot.mcf88.cloud/LoRaWeb/#/configuration|LoRaWEB Tool]]
Line 462: Line 463:
 |MCF-LW13MIO-WW | enginko LoRa multi I/O module   2.4GHz | |MCF-LW13MIO-WW | enginko LoRa multi I/O module   2.4GHz |
  
-===== 11 Declaration of conformity =====+===== 11 Declaration of conformity =====
  
-Hereby, enginko Srl declares that MCF-LW13MIO complies with the essential requirements and other relevant provisions of Directive  2014/53/EU.+Declarations of conformity are available from Angel4Future by sending a request email to sensors@enginko.com.
  
  
 ===== 12 Contacts ===== ===== 12 Contacts =====
  
-**enginko Srl** \\  +**Angel4Future S.r.l.** \\  
-Via Roma 3  I-28060 Sozzago (NO) \\  +Via San Sabino 21 70042 MOLA DI BARI (BA, ITALY \\  
-T  :    +39 0321 15 93 088 \\  +T  :    +39 080 532 1796 \\  
  
-E  :    info@enginko.com  \\  +E  :    info@angel4future.com  \\ 
-PEC: enginkosrl@legalmail.it \\ +
 W:     enginko.com \\  W:     enginko.com \\